dc.contributor.authorAraujo G., Betsy A.-
dc.contributor.authorLara L., Gerardo M.-
dc.date.accessioned2014-06-10T21:32:27Z-
dc.date.available2014-06-10T21:32:27Z-
dc.date.issued2014-06-10-
dc.identifier.urihttp://hdl.handle.net/10872/6579-
dc.description.abstractSe realizó el análisis exergético de un equipo de acondicionamiento de aire, el cual opera con carga variable de refrigerante, compuesto por un compresor de velocidad variable, otro de velocidad constante, un condensador y múltiples evaporadoras con válvulas electrónicas lineales de expansión. Se procedió a realizar el estudio calculando las variables termodinámicas por el enunciado de la Primera Ley y con ajustes de curvas de las propiedades del refrigerante R-22, posteriormente, calculando las irreversibilidades en cada uno de los componentes y su eficiencia exergética. Se tomó la data de las variables termodinámicas con el programa que opera el equipo (LGMV), el cual recibe la información por sensores ubicados a lo largo del sistema, así también se recopiló el consumo eléctrico correspondiente al funcionamiento, con diferentes condiciones en el recinto y ambiente exterior, usando hojas de cálculos se obtuvieron las irreversibilidades, flujos exergéticos, y eficiencia exergética, finalizando con la elaboración de gráficas. Se recomendaron mejoras en los procesos del equipo para así disminuir las pérdidas reflejadas.es_VE
dc.description.abstractAn exergetic analysis of an air conditioning equipment was carried out. The equipment works with refrigerant variable load. It is made up of a variable speed compressor, an additional constant speed compressor, besides of a condenser and multiple expansion linear electronic valve evaporators. The study was accomplished by calculating the thermodynamic variables using the First Law statement and with curve adjustments from the R-22 refrigerant properties. Subsequently, the irreversibility and exergetic efficiency was calculated at each of the components. Data for the thermodynamic variables were measured with the equipment operating program (LGMV), which receives the information through out sensors located all along the system. The operating power consumption was gathered in the same manner, with different conditions inside and external surroundings. The irreversibilities, exergetic flows and efficiency as well as final graphs were obtained with the use of spread sheets. Improvement in the equipment processes were recommended in order to diminish the registered losses.es_VE
dc.language.isoeses_VE
dc.relation.ispartofseriesTesis A11;2009-
dc.subjectExergíaes_VE
dc.subjectAire Acondicionadoes_VE
dc.subjectCompresor Inversores_VE
dc.subjectVelocidad Variablees_VE
dc.subjectCarga Variablees_VE
dc.subjectR-22es_VE
dc.subjectRefrigeraciónes_VE
dc.subjectCompresión de Vapores_VE
dc.subjectExergyes_VE
dc.subjectAir Conditioneres_VE
dc.subjectInverter Compressores_VE
dc.subjectVariable Speedes_VE
dc.subjectVariable Loades_VE
dc.subjectRefrigerationes_VE
dc.subjectSteam Compressiones_VE
dc.titleAnálisis exergénico de un equipo de acondicionamiento de aire de carga variable de refrigerantees_VE